     1.Battery Introduced
     1.1 Standard Series
     1.2 Longevity Series
     1.3 Deep Cycle
     1.4 High Temperature
     2.Characteristics
     3.General
     3.1 Discharge
     3.2 Charging
     3.3 Life
     3.4 Storage
     4.Data Table
     5.Terminals Size
     6.User Manual
     7.Production flow
¡¡

  3.General

¡¡¡¡3.1 Discharge

¡¡¡¡3.1.1 Termination voltage £º
¡¡¡¡To ensure the safety and the largest battery life. termination of the discharge voltage and current of the battery discharge, discharge current, termination of some low battery voltage, current and discharge the contrary, the battery voltage is higher termination. (Table 1) at different rates -- recommended termination voltage discharge.

Current
Termination voltage£º(VPC)
< 0.1CA
1.75
0.11-0.17CA
1.70
0.18-0.25CA
1.67
0.26-1CA
1.60
> 1.1CA
1.30

¡¡¡¡3.1.2 Capacity :
¡¡¡¡The discharge capacity of the main battery and discharge current and temperature of the environment
¡¡¡¡Battery capacity and discharge current relationship £º
(Figure 1-3) FP, LFP, CFP type batteries Discharge rate in the capacity released under conditions that can be seen from the map, the greater the discharge rate. The smaller capacity batteries can emit.







¡¡¡¡3.1.3 Battery capacity and the relationship between temperature £º ¡¡¡¡
¡¡¡¡Change in the discharge current, temperature, battery discharge capacity, that the low-temperature, battery discharge capacity less (Figure 4) for battery capacity and temperature curve.